38/66kV High Voltage Cable: Specifications, Construction, and Selection Guide

A 38/66kV high voltage cable is designed for power networks with a rated phase-to-earth voltage of 38 kV and a rated phase-to-phase voltage of 66 kV; the associated maximum system voltage is commonly designated as 72.5 kV. Choosing the right cable means confirming more than its voltage label: conductor size and material, insulation system, metallic screen, installation conditions, applicable standards, and accessories must all suit the project. In this guide, we explain the main specifications and construction options, show how to match a cable to its application, and outline what to check when evaluating a supplier.

Click here to get more.

Who This Guide Is For

We prepared this guide for utility engineers, EPC contractors, electrical consultants, distributors, and procurement teams involved in medium- and high-voltage power projects. It is intended to support early specification and supplier discussions, not replace a project design or a review by a qualified electrical engineer. Requirements can differ by country, network operator, installation method, and governing standard, so final cable selection should follow the approved project documents.

Understanding the 38/66kV Cable Rating

What the voltage designation means

In the designation 38/66 (72.5) kV, the first value, 38 kV, is the rated voltage between a conductor and earth, usually written as U0. The second value, 66 kV, is the rated voltage between conductors, or U, while 72.5 kV represents the maximum system voltage, Um, for the relevant rating convention. Confirm that the notation on a quotation or datasheet matches the project’s required voltage class and terminology.

Voltage class is only one part of cable suitability. The cable must also be selected for load current, short-circuit duty, system earthing, route length, installation environment, and the electrical characteristics of the network. For this voltage range, project specifications may refer to standards intended for high-voltage extruded-insulation cable systems; the buyer should identify the required standard and edition rather than assume that every cable labeled 38/66kV has an identical design.

Construction and Material Options

Typical single-core cable layers

A typical extruded-insulation design includes a conductor, conductor screen, insulation, insulation screen, metallic screen or sheath, and outer sheath. The conductor screen and insulation screen help create a controlled electrical interface around the insulation. The metallic layer provides a path for charging and fault currents when correctly bonded, while the outer sheath protects underlying layers from the installation environment.

Copper and aluminium are common conductor material options, but their suitability depends on the required current capacity, cable dimensions, termination compatibility, and project economics. Insulation is commonly based on cross-linked polyethylene (XLPE) in this voltage class, although the project specification determines the acceptable material and design. Water-blocking components, armouring, and sheath compounds may be added where route conditions or purchaser requirements call for them.

Single-core or three-core configuration

Single-core cables are widely used in high-voltage transmission and distribution installations, with the final arrangement depending on circuit design and installation constraints. Three-core construction may be considered for some projects, but it is not automatically interchangeable with a single-core system. The buyer should assess cable handling, route space, installation method, bonding arrangement, and the requirements for joints and terminations before fixing the configuration.

Specifications to Confirm Before Ordering

A useful datasheet review starts with the full electrical and construction specification, not just a product name. The values below are items to confirm with the project design team and supplier; there is no universal conductor size or sheath design that fits every 38/66kV installation.

Specification area What to confirm Why it matters
Voltage and standard U0/U (Um), applicable standard, and required edition Establishes the intended electrical rating and design basis.
Conductor Copper or aluminium, cross-sectional area in mm², and conductor construction Affects current capacity, resistance, cable dimensions, and connection requirements.
Insulation system Insulation material, thickness, and electrical test requirements Must align with the rated voltage and project specification.
Metallic layer Screen or sheath material, cross-section, and bonding arrangement Influences earthing, fault-current performance, and induced-voltage management.
Outer protection Sheath material, colour, water-blocking, and any armour requirement Addresses the mechanical and environmental conditions along the route.
Delivery and accessories Drum length, joints, terminations, packing, and documentation Supports installation planning and avoids gaps between cable and accessory requirements.

Matching Cable Design to the Application

For underground routes, assess soil thermal properties, burial depth, grouping with other circuits, duct configuration, and water exposure. These factors affect heat dissipation and may change the allowable current, so conductor size should be established through the project’s electrical and thermal calculations. Confirm whether the route includes sections with different installation conditions, since one nominal cable selection may need to account for the most limiting section.

For outdoor or substation connections, the design team should consider how the cable interfaces with switchgear, transformers, overhead-line transitions, and terminations. Cable support, bending limits, sealing, and the environmental rating of accessories are also relevant. A technically suitable cable can still create installation difficulties if the accessory system or route arrangement is not coordinated early.

For every application, clarify the network’s fault conditions and earthing approach. The metallic screen or sheath design must be considered alongside bonding and protection arrangements, rather than selected in isolation. Where the route is long or includes parallel circuits, request engineering review of the applicable screen and bonding design from the project team.

You will get efficient and thoughtful service from Zhongdong Cable Co., Ltd..

A Practical Selection Framework

  1. Define the network requirement. Record the required voltage designation, operating conditions, system frequency, earthing method, and governing standard. Resolve any differences between the project specification and utility requirements before requesting a final quotation.

  2. Describe the route and installation. Provide route length, installation method, ambient conditions, grouping, burial or duct details, and any demanding environmental exposure. Share drawings or route schedules where available, while marking assumptions that remain open.

  3. Confirm electrical sizing and construction. Have the responsible design team determine conductor cross-section and check current capacity, voltage drop where applicable, and short-circuit duty. Then specify conductor material, insulation system, screen, sheath, and any water-blocking or armour requirements.

  4. Coordinate accessories and installation data. Check that joints, terminations, bonding components, and cable dimensions fit the system design and site constraints. Request the relevant technical drawings, handling guidance, and drum information for installation planning.

  5. Review the offer against the specification. Compare each supplier’s datasheet line by line, including deviations, test documentation, quantity, delivery basis, and exclusions. Ask for clarification in writing when an offer uses a different standard, construction, or accessory scope.

Pricing, Minimum Order Quantity, and Lead Time

There is no reliable universal price for 38/66kV cable because cost depends on the conductor material and size, cable construction, order quantity, drum length, accessories, testing requirements, and delivery destination. Minimum order quantities and production schedules are likewise supplier- and project-specific. Buyers should request a quotation based on a complete technical specification and confirm whether quoted lead time begins after technical approval, order confirmation, or another agreed milestone.

For a more comparable commercial review, ask suppliers to identify the exact cable construction, unit of measurement, included accessories, packing method, inspection scope, and shipping terms. Clarify whether the quotation is for cable only or includes engineering documents and accessory support. These details help procurement teams compare offers on scope rather than headline price alone.

Supplier Evaluation Checklist

When assessing a supplier, request a technical datasheet, construction details, applicable standard references, and a clear list of deviations from your specification. Ask how the supplier handles technical clarification, document approval, production updates, inspection requests, packing, and export coordination. Any quality claims, test records, or compliance documents should be reviewed against the project’s actual requirements and verified as part of procurement.

At Zhongdong Cable Co., Ltd., we support B2B buyers by discussing cable requirements and reviewing the information needed to define a suitable quotation. Share the target voltage, conductor material and size if known, route conditions, applicable standard, quantity, destination, and accessory scope. We can then assess the request with you and clarify product configuration, documentation, and delivery details subject to project and order confirmation.

Key Takeaways and Next Steps

A 38/66kV cable is identified by a 38 kV conductor-to-earth rating and a 66 kV conductor-to-conductor rating, commonly associated with a 72.5 kV maximum system voltage. The final design depends on conductor sizing, insulation and screen construction, installation conditions, fault requirements, accessories, and the standards specified for the project. No single cable size or construction should be selected from the voltage designation alone.

To move forward, prepare the project specification, route information, estimated quantity, required documents, and delivery destination before requesting offers. Ask each supplier to identify deviations and confirm the cable-and-accessory scope in writing. Zhongdong Cable Co., Ltd. welcomes project enquiries from buyers seeking to evaluate 38/66kV high voltage cable options and supplier support for their application.